0102030405
China JDZ(18)-3, 6, 10 Type Voltage Transformers - Reliable Suppliers and Factory for 3-10kV AC Power Systems
Model and Its Meaning
Overview
⚡ Voltage transformers (VTs) play a vital role in the operation and safety of AC power systems, particularly those operating at a rated frequency of 50Hz or 60Hz and with a rated voltage range of 3–10kV. These devices are designed for energy metering, voltage measurement, and relay protection, ensuring efficient and safe power system operation. Voltage transformers comply with GB20840.1-2010 and GB20840.3-2013 standards, providing reliable solutions for a variety of applications in industrial and commercial environments.
Normal Service Conditions
🏢
Installation Site: Indoor
🌡️
Ambient Temperature: Maximum temperature is 40℃, minimum temperature is -5℃, and the daily average temperature does not exceed 30℃.
🌤️
Atmospheric Conditions: There is no severe pollution in the atmosphere.
Technical Parameters
Product |
Rated Voltage |
Accuracy |
Rated |
Extreme |
Rated Insulation |
JDZ(18)-3 |
3/0.1 |
0.2 |
15 |
200 |
3.6/25/40 |
0.5 |
30 |
||||
JDZ(18)-6 |
6/0.1 |
0.2 |
15 |
200 |
7.2/32/60 |
0.5 |
30 |
||||
JDZ(18)-10 |
10/0.1 |
0.2 |
15 |
200 |
12/42/75 |
0.5 |
30 |
||||
JDZ(18)-3 |
3/0.1/0.22 |
0.2/3 |
15/500 |
600 |
3.6/25/40 |
0.5/3 |
30/500 |
||||
JDZ(18)-6 |
6/0.1/0.22 |
0.2/3 |
15/500 |
600 |
7.2/32/60 |
0.5/3 |
30/500 |
||||
JDZ(18)-10 |
10/0.1/0.22 |
0.2/3 |
15/500 |
600 |
12/42/75 |
0.5/3 |
30/500 |
Structure and Characteristics
This series of voltage transformers adopt a pillar structure and are fully enclosed with epoxy resin by epoxy casting. Key features include:
- 🛡️ Resistant to pollution and moisture, and suitable for use in tropical regions.
- 🔧 No special maintenance required — only regular cleaning of surface dirt is needed.
- 🔌 Terminal boxes are installed at the secondary output terminals. One hole on the front and one on the side of the terminal box cooperate with the output terminals for leadout wiring, ensuring safe and reliable connections.
- ⚙️ Equipped with grounding bolts and six installation holes for secure mounting on the product base plate.
Frequently Asked Questions (FAQ)
❓
What are the rated voltage options available for the JDZ(18) series voltage transformers?
The JDZ(18) series is available in three rated voltage models: JDZ(18)-3 (3kV), JDZ(18)-6 (6kV), and JDZ(18)-10 (10kV), with corresponding voltage ratios of 3/0.1, 6/0.1, and 10/0.1 respectively. Dual secondary winding versions with ratios such as 3/0.1/0.22, 6/0.1/0.22, and 10/0.1/0.22 are also available.
❓
What accuracy levels are available for the JDZ(18) series?
The JDZ(18) series voltage transformers are available in accuracy levels 0.2 and 0.5 for single secondary winding models, and 0.2/3 and 0.5/3 for dual secondary winding models. The 0.2 level is ideal for precision energy metering, while the 0.5 level is suitable for general measurement and relay protection.
❓
What standards do the JDZ(18) series voltage transformers comply with?
The JDZ(18) series voltage transformers comply with Chinese national standards GB20840.1-2010 (general requirements for instrument transformers) and GB20840.3-2013 (specific requirements for inductive voltage transformers), ensuring product quality and safety.
❓
Are the JDZ(18) voltage transformers suitable for humid or tropical environments?
Yes. The JDZ(18) series uses a fully enclosed epoxy resin casting design, which provides excellent resistance to moisture and pollution. This makes them well-suited for use in tropical regions and environments with higher humidity levels, though they are designed for indoor installation.
❓
What maintenance is required for the JDZ(18) series voltage transformers?
The JDZ(18) series requires minimal maintenance. No special maintenance procedures are needed during normal operation. It is only necessary to perform regular cleaning of surface dirt to maintain performance and appearance. This low-maintenance design reduces operational costs over the product's lifetime.
❓
What is the operating temperature range for the JDZ(18) series?
The JDZ(18) series voltage transformers are designed to operate within an ambient temperature range of -5℃ to +40℃, with a daily average temperature not exceeding 30℃. They are intended for indoor installation in environments free from severe atmospheric pollution.