China LZZB9-24/180b/2(Series Current Transformers - Reliable Power Measurement Solutions from Suppliers & Factory
Model and its Meaning
Summarize
A key highlight of the 15-40.5kV indoor current transformer is its superior insulation performance. Rated insulation voltages up to 40.5/95/185kV, these transformers are designed to withstand the harsh conditions of high-voltage environments. For example, the creepage distance of the LZZB9-35 and 40.5 type current transformers is as long as 851mm, effectively preventing insulation breakdown. This characteristic is crucial for ensuring the safe and reliable operation of the transformer, as it minimizes the risk of electrical faults that could lead to catastrophic failures.
In addition to its superior insulation performance, this current transformer also boasts excellent environmental adaptability. Its design resists pollution and humidity, making it suitable for harsh indoor environments. This adaptability is crucial for maintaining performance in a variety of climates, including tropical regions. This 15-40.5kV indoor current transformer operates normally within a temperature range of -5℃ to 40℃, further highlighting its versatility and enabling its widespread application and stable performance in diverse environments.
Normal Service Condition
Indoor, suitable for use in various environments such as power equipment and control rooms, to ensure the safe and stable operation of equipment and provide good working conditions.
Maximum temperature 40℃; minimum temperature -5℃; daily average temperature not exceeding 30℃, to adapt to climate changes in different seasons, ensure normal operation of equipment under various temperature conditions, and avoid performance impact due to excessively high or low temperatures.
The atmosphere is free of severe pollution, ensuring that the equipment operates in a good environment, thereby improving its reliability and service life, reducing the possibility of failure, and ensuring the stability of the power system.
Technical Parameter
LZZB9-24/180b/2 Technical Parameter Table
| Product model | Rated primary current (A) | Accuracy level combination | Rated output (VA) | Rated short-term thermal current (kA) | Rated dynamic stability current (kA) |
|---|---|---|---|---|---|
| LZZB9-24/180b/2 | 20 | 0.2/0.2 0.2/0.5 0.2/10P10 0.5/10P10 0.2/10P15 0.5/10P15 |
15/15 15/20 10/20 15/20 10/15 15/15 |
3 | 7.5 |
| 30 | 4.5 | 11.25 | |||
| 40 | 6 | 15 | |||
| 50 | 7.5 | 18.75 | |||
| 75 | 11.25 | 28.125 | |||
| 100 | 15 | 37.5 | |||
| 150 | 22.5 | 56.25 | |||
| 200 | 31.5 | 80 | |||
| 300 | 45 | 112.5 | |||
| 400 | |||||
| 500 | |||||
| 600 | 0.2/0.2 0.2/0.5 0.2/10P10 0.5/10P10 0.2/10P15 0.5/10P15 0.2S/10P30 |
15/15 15/20 10/20 15/20 10/15 15/15 15/15 |
63 | 130 | |
| 800 | |||||
| 1000 | 80 | 160 | |||
| 1200 | |||||
| 1250 |
LZZB9-24/180b/4 Technical Parameter Table
| Product model | Rated primary current (A) | Accuracy level combination | Rated output (VA) | Rated short-term thermal current (kA) | Rated dynamic stability current (kA) |
|---|---|---|---|---|---|
| LZZB9-24/180b/4 | 20 | 0.2/0.2/0.2 0.2/0.5/0.5 0.2/10P10/10P10 0.5/10P10/10P10 0.2/10P15/10P15 0.5/10P15/10P15 |
10/10/10 10/10/10 10/15/15 10/15/15 10/10/15 10/10/15 |
3 | 7.5 |
| 30 | 4.5 | 11.25 | |||
| 40 | 6 | 15 | |||
| 50 | 7.5 | 18.75 | |||
| 75 | 11.25 | 28.125 | |||
| 100 | 15 | 37.5 | |||
| 150 | 22.5 | 56.25 | |||
| 200 | 31.5 | 80 | |||
| 300 | 45 | 112.5 | |||
| 400 | |||||
| 500 | |||||
| 600 | 0.2/0.2/0.2 0.2/0.5/0.5 0.2/10P10/10P10 0.5/10P10/10P10 0.2/10P15/10P15 0.5/10P15/10P15 0.2S/0.5/15P30/15P30 |
10/10/10 10/10/10 10/15/15 10/15/15 10/10/15 10/10/15 15/15/15/15 |
63 | 130 | |
| 800 | |||||
| 1000 | 80 | 160 | |||
| 1200 | |||||
| 1250 |
Structure and Characteristics
This series of current transformers features a fully enclosed epoxy resin casting structure, providing excellent insulation and moisture resistance, ensuring stable operation under various environmental conditions. The product boasts a compact structure, small size, light weight, and easy surface cleaning, facilitating daily maintenance and management. A terminal box is installed at the secondary output terminals, ensuring safety and reliability and effectively preventing wiring faults. The base plate includes a grounding bolt and six mounting holes, a rational design that allows for flexible installation and fixation to meet diverse installation needs.

JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits