China LZZBJ9-12/175b/2(Series Current Transformers - Trusted Suppliers & Factory for Reliable Power Solutions
Model and its meaning
Summarize
Current transformers must be operated within specified normal operating conditions. They should be installed indoors in a temperature-controlled environment. They are designed to operate within a temperature range of -5°C to 40°C, with an average daily temperature not exceeding 30°C. These conditions are crucial to ensuring the lifespan and reliability of the current transformer, as extreme temperatures can adversely affect its performance and accuracy.
Normal service condition
Technical parameter
LZZBJ9-12/175b/2 Type Technical parameter table of Current Transformer
| Product model | Rated primary current | Accuracy level combination | Rated output | Rated short-term thermal current | Rated dynamic stability current |
|---|---|---|---|---|---|
| LZZBJ9-12/175b/2 | 5 | 0.2/10P10 0.5/10P10 0.2/10P15 0.5/10P15 0.2S/10P30 |
10/15 10/15 10/15 15/15 15/15 |
0.6 | 1.5 |
| 10 | 1.2 | 3 | |||
| 15 | 1.8 | 4.5 | |||
| 20 | 2.4 | 6 | |||
| 30 | 3.6 | 9 | |||
| 40 | 4.8 | 12 | |||
| 50 | 6 | 15 | |||
| 75 | 9 | 22.5 | |||
| 100 | 12 | 30 | |||
| 150 | 18 | 45 | |||
| 200 | 21 | 52.5 | |||
| 300 | 0.2/10P10 0.5/10P10 0.2/10P15 0.5/10P15 0.2S/10P30 |
10/15 10/15 10/20 15/20 15/15 |
24.5 | 61.25 | |
| 400 | 32 | 80 | |||
| 500 | |||||
| 600 | |||||
| 800 | 0.2/10P10 0.5/10P10 0.2/10P15 0.5/10P15 0.2S/10P30 |
15/20 15/20 15/20 30/20 15/15 |
50 | 125 | |
| 1000 | |||||
| 1200 | |||||
| 1250 | |||||
| 1500 | 0.2/10P10 0.5/10P10 0.2/10P15 0.5/10P15 0.2S/10P30 |
15/20 15/20 20/20 30/20 15/15 |
63 | 157.5 | |
| 2000 | |||||
| 2500 | |||||
| 3000 | |||||
| 3150 |
LZZBJ9-12/175b/4 Type Technical parameter table of Current Transformer
| Product model | Rated primary current | Accuracy level combination | Rated output | Rated short-term thermal current | Rated dynamic stability current |
|---|---|---|---|---|---|
| LZZBJ9-12/175b/4 | 5 | 0.2/0.2/5P10 0.2/0.5/5P15 0.2/0.5/5P20 0.2/5P10/10P15 0.5/5P10/10P20 0.2S/0.5/5P30/5P30 |
10/10/20 10/10/15 10/10/15 10/15/15 10/15/15 10/10/15/15 |
0.6 | 1.5 |
| 10 | 1.2 | 3 | |||
| 15 | 1.8 | 4.5 | |||
| 20 | 2.4 | 6 | |||
| 30 | 3.6 | 9 | |||
| 40 | 4.8 | 12 | |||
| 50 | 6 | 15 | |||
| 75 | 9 | 22.5 | |||
| 100 | 12 | 30 | |||
| 150 | 18 | 45 | |||
| 200 | 21 | 52.5 | |||
| 300 | 0.2/0.2/5P10 0.2/0.5/5P15 0.2/0.5/5P20 0.2/5P10/10P15 0.5/5P10/10P20 0.2S/0.5/5P30/5P30 |
10/10/20 10/10/20 10/15/15 10/15/20 15/15/15 10/10/15/15 |
24.5 | 61.25 | |
| 400 | 32 | 80 | |||
| 500 | |||||
| 600 | 0.2/0.2/5P10 0.2/0.5/5P15 0.2/0.5/5P20 0.2/5P10/10P15 0.5/5P10/10P20 0.2S/0.5/5P30/5P30 |
10/10/20 10/10/15 10/10/15 10/15/15 15/15/15 10/10/15/15 |
32 | 80 | |
| 800 | 50 | 125 | |||
| 1000 | 0.2/0.2/5P10 0.2/0.5/5P15 0.2/0.5/5P20 0.2/5P10/10P15 0.5/5P10/10P20 0.2S/0.5/5P30/5P30 |
10/10/30 15/15/20 15/20/20 10/15/15 15/15/20 10/10/15/15 |
50 | 125 | |
| 1200 | |||||
| 1250 | |||||
| 1500 | 63 | 157.5 | |||
| 2000 | |||||
| 2500 | 0.2/0.2/5P10 0.2/0.5/5P15 0.2/0.5/5P20 0.2/5P10/10P15 0.5/5P10/10P20 0.2S/0.5/5P30/5P30 |
15/15/30 15/15/20 15/20/20 15/15/20 15/20/15 10/10/15/15 |
63 | 157.5 | |
| 3000 | 0.2/0.2/5P10 0.2/0.5/5P15 0.2/0.5/5P20 0.2/5P10/10P15 0.5/5P10/10P20 0.2S/0.5/5P30/5P30 |
15/15/30 15/15/20 15/30/20 15/15/20 15/20/15 10/10/15/15 |
63 | 157.5 | |
| 3150 |
Rated secondary current: 5A or 1A, rated insulation level: 12/42/75kV.
Structure and characteristics
This series of current transformers utilizes a fully enclosed epoxy resin cast structure, exhibiting excellent insulation and moisture resistance. Its compact design, small size, and light weight make it easy to clean and maintain. The secondary terminals are equipped with a terminal block for safety and reliability. The baseplate is equipped with a grounding bolt and six mounting holes for flexible installation.