DGLR Series Isolation Switch Fuse Group - High-Quality China Suppliers Factory for AC 690V, Up to 1250A
Meaning of Product Model
Normal Working and Installation Conditions
●
1. The ambient air temperature shall not exceed +40℃ and not be lower than -5℃.
●
2. The altitude of the installation site shall not exceed 2000m.
●
3. Humidity: When the maximum temperature is +40℃, the relative humidity of the air does not exceed 50%. Higher relative humidity can be allowed at lower temperatures, such as reaching 90% at 20℃. Special measures should be taken for occasional condensation caused by temperature changes.
●
4. The pollution level of the surrounding environment is level 3.
●
5. The switch should be installed in a place without significant shaking, impact vibration, and invasion of rain and snow. At the same time, the installation location should be free of explosive hazardous media, and there should be no gas or dust in the media that can corrode metals and damage insulation.
Structure Characteristics
✓
1. The acceleration mechanism with instantaneous release of spring energy storage achieves fast connection or disconnection, independent of the speed of the operating handle, and improves the ability to extinguish arcs.
✓
2. The shell made of unsaturated polyester glass fiber reinforced plastic (DMC) has good flame retardancy, dielectric properties, and operational safety.
✓
3. Parallel multi break contact has self-cleaning function and reliable overcurrent and short-circuit safety protection function.
✓
4. Can ensure that the circuit is connected or disconnected with load.
✓
5. Replacing the melt is safe, convenient, and fast.
Main Technical Parameters
Relationship between switches and fuses
| Agreed heating current lth | Equipped with fuse code | Rated current of fuse (A) |
|---|---|---|
| 63 | NT00C、NH00C | 4、6、10、16、20、25、32、40、50、63 |
| 125 | NT00、NH00 | 10、16、20、25、32、40、50、63、125 |
| 160 | NT00、NH00 | 10、16、25、32、40、50、63、80、100, 125、160 |
| 250 | NT1、NH1 | 63、80、100、125、160、200、250 |
| 400 | NT2、NH2 | 160、200、250、315、400 |
| 630 | NT3、NH3 | 250、315、400、500、630 |
| 800 | NT4、NH4 | 800 |
| 1000 | NT4、NH4 | 800、1000 |
| 1250 | NT4、NH4 | 800、1000、1250 |
Main technical parameters of switches
| Model specifications | DGLR-63 | DGLR-125 | DGLR-160 | DGLR-250 | DGLR-400 | DGLR-630 | DGLR-800 | DGLR-1000 | DGLR-1250 | ||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Agreed heating current (A) | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | ||
| Rated insulation voltage (V) | 800 | 800 | 800 | 800 | 800 | 800 | 800 | 800 | 800 | ||
| Rated impulse withstand voltage (kV) | 4 | 4 | 4 | 4 | 8 | 8 | 8 | 8 | 8 | ||
| Rated working current (A) | 380V | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | |
| 660V | 63 | 100 | 125 | 200 | 315 | 500 | 630 | 800 | 1000 | ||
| Rated making/breaking capacity(A) | AC660V,AC-23B | Connect | 630 | 1250 | 1600 | 2500 | 4000 | 6300 | 8000 | 10000 | 12500 |
| AC660V,AC-23B | Breaking | 504 | 1000 | 1280 | 2000 | 3200 | 5040 | 6400 | 8000 | 10000 | |
| Mechanical lifespan (times) | 1400 | 1400 | 1400 | 1400 | 800 | 800 | 500 | 500 | 500 | ||
| Electrical lifespan (times) | 200 | 200 | 200 | 200 | 200 | 200 | 100 | 100 | 100 | ||
| Operating Force (N) | 7.5 | 16 | 16 | 16 | 30 | 30 | 40 | 40 | 40 | ||
| Rated limit short circuit current(KA) | 50 | 50 | 50 | 50 | 50 | 50 | 100 | 100 | 100 | ||
Installation Precautions
1. The contact parameters of the switch have been set by the manufacturer and cannot be adjusted freely during use.
2. During the connection process between the busbar and the product, it is necessary to ensure that the distance between the busbar holes is consistent with the product wiring holes to avoid product damage caused by external forces.
Ordering Notice
Customers are required to indicate the product name, model, rated current, number of poles, and quantity. For example, DGLR-400/3C11, equipped with 315A fuses, quantity of 10 units.
Note: The specifications and external dimensions may change due to product improvements without further notice, and the actual product shall prevail.
Note: The specifications and external dimensions may change due to product improvements without further notice, and the actual product shall prevail.
Frequently Asked Questions
Q1: What is the operating temperature range for the DGLR switch?
The ambient air temperature should be between -5℃ and +40℃ for normal operation.
Q2: Can the DGLR series switch handle load during disconnection?
Yes, the structure is designed to ensure that the circuit can be connected or disconnected safely even with a load.
Q3: What material is used for the switch shell?
The shell is made of DMC (unsaturated polyester glass fiber reinforced plastic), providing excellent flame retardancy and dielectric properties.
Q4: What is the maximum installation altitude for these switches?
The installation site altitude should not exceed 2000 meters to ensure optimal performance.
Q5: Is the fuse replacement process complicated?
No, the design allows for safe, convenient, and fast replacement of the melt/fuse.
Q6: What information is needed when placing an order?
Please provide the product name, model, rated current, number of poles, and the specific quantity required.