DH Series 3 Phase Fuse Switch Disconnector 160A 250A 400A 630A Switch-Disconnector
Meaning of Product Model

Normal Working and Installation Conditions
1、The ambient air temperature shall not exceed +40℃ and not be lower than-5℃.
2、The altitude of the installation site shall not exceed 2000m.
3、Humidity: When the maximum temperature is +40℃ , the relative humidity of the air does not exceed 50%. Higher relative humidity can be allowed at lower temperatures, such as reaching 90% at 20℃. Special measures should be taken for occasional condensation caused by temperature changes.
4、The pollution level of the surrounding environment is level 3.
5、The switch should be installed in a place without significant shaking, impact vibration, and invasion of rain and snow. At the same time, the installation location should be free of explosive hazardous media, and there should be no gas or dust in the media that can corrode metals and damage insulation.
Structure Characteristics
The product has a beautiful and innovative design. The switch is composed of a base, cover, and arc extinguishing chamber, all of which are made of arc resistant plastic and have a fully plastic structure. The static contact is directly installed on the base, and the arc extinguishing chamber is easy to disassemble. Each uses multiple arc extinguishing grids, enhancing the arc extinguishing ability and improving the contact life. The NT type fuse is installed inside the cover, which rotates in a fan-shaped manner and has a large electrical isolation distance to meet the requirements of the isolation switch. The cover can be easily removed from the base. On both sides of the switch, auxiliary contacts can be installed as needed to send signals indicating the opening and closing status of the switch.
Main Technical Specifications
Relationship between switches and fuses
| Conventional thermal current lth | Matching fuse size | Rated current of fuse link (A) |
| 160 | NT00,NH00 | 10、16、25、32、40、50、63、80、100、125、160 |
| 250 | NT1,NH1 | 63、80、100、125、160、200、250 |
| 400 | NT2,NH2 | 160、200、250、315、400 |
| 630 | NT3,NH3 | 250、315、400、500、630 |
Main technical parameters of switches
| Model Specifications | DH00-160 | DH01-250 | DH02-400 | DH03-630 | ||
| Conventional Thermal Current(A) | 160 | 250 | 400 | 630 | ||
| Rated Insulation Voltage Ui (V) | 1000 | 1000 | 1000 | 1000 | ||
| Rated Impulse Withstand Voltage (kV) | 12 | 12 | 12 | 12 | ||
| Rated Working Current(A) | 500V | 160 | 250 | 400 | 630 | |
| 690V | 125 | 200 | 315 | 500 | ||
| Rated making and breaking capacity(A) (1.05Ue) | AC500V,AC-22B COSΦ:0.65 | Connect | 480 | 750 | 1200 | 1890 |
| AC500V,AC-22B COSΦ:0.65 | Breaking | 480 | 750 | 1200 | 1890 | |
| Mechanical Life (Time) | 1400 | 800 | 800 | 800 | ||
| Electrical Life (Time) | 200 | 200 | 200 | 200 | ||
| Operating Force (N) | ≤400 | ≤400 | ≤400 | ≤400 | ||
| Rated Conditional Short-circuit Current (kA) (AC-21B/AC-22B) | 50/120 | 50/120 | 50/120 | 50/120 | ||
| Usage Category | 500V:AC22B 690V:AC21B |
500V:AC22B 690V:AC21B |
500V:AC22B 690V:AC21B |
500V:AC22B 690V:AC21B |
||
| Pollution Degree | 3 | 3 | 3 | 3 | ||
| Degrees of Protection Provided by Enclosure | IP30 | IP30 | IP30 | IP30 | ||
Installation Precautions
1.The contact parameters of the switch have been set by the manufacturer and cannot be adjusted freely during use.
2.During the connection process between the busbar and the product, it is necessary to ensure that the distance between the busbar row holes is consistent with the product wiring holes to avoid product damage caused by external forces.
Ordering Information
Customers must indicate the product name, model, rated current, pole number and quantity,Example 1: DH02-400/31(equipped with fuse: 315A,with microswitch) Quantity:10 units;
Note: The specifications and dimensions are subject to change due to product improvements without prior notice, and the actual product shall prevail.
Wiring Terminal Accessories
| Terminal Shape | Terminal Model | Torque N*M | Cable size mm² | Can be equipped with switch models |
| M8 bolt (with wiring nose) | 12-15 | 16-70 | DH-160 | |
| M10 bolt (with wiring nose) | 30-35 | 25-150 | DH-250~400 | |
| M12 bolt (with wiring nose) | 35-40 | 25-240 | DH-630 | |
![]() |
XYDZ001 | 3 | 16-70 s(r) 16-70 s(s) 16-70 f+AE |
DH-160 |
![]() |
XYDZ002 | 6 | 75-150 s(r) 75-150 s(s) 75-150 f,f+AE |
DH-250 |
![]() |
XYDZ004 | 8 | 50-240 s(r) 50-240 s(s) 50-240f,f+AE |
DH-630 |