Zhejiang Donghua Electrical Appliance Co., Ltd.
Leave Your Message
Products Categories
Featured Products

HDR black series SMPS,Single Output Industrial, DIN Rail Power Supply

Designed for demanding industrial environments, the DR Series Single Output DIN Rail Power Supply delivers robust, reliable performance in a compact form factor. Featuring universal AC input, comprehensive protections, and a wide operating temperature range, it ensures stable power for control systems, PLCs, sensors, and automation equipment. Easy to install on standard DIN rails and backed by a 3-year warranty, this unit combines efficiency with durability for long-term operation.

Product Model: HDR-30, HDR-45, HDR-60, HDR-15S, HDR-30S, HDR-60S, HDR-100S, HDR-75, HDR-120, HDR-240, HDR-480, NDR-75, NDR-120, NDR-240, NDR-480.

    Product Model Meaning

    HS HRs single output switching Power supply.jpg

    Product Introduction

    Built to meet the needs of modern industrial applications, the DR Series power supply offers a dependable and efficient solution for delivering stable DC power. Its compact design saves valuable panel space while maintaining high reliability, making it ideal for integration into control cabinets, machinery, and automation systems.

    Engineered for performance and longevity, this power supply operates efficiently across a broad ambient temperature range of -25°C to +70°C. For optimal service life, we recommend maintaining the operational load between 20% and 80% of its rated capacity, and ensuring at least 5 cm of clearance around the unit to support effective heat dissipation. It accepts a wide input voltage range—typically AC 100-240V—allowing flexible deployment across different regions and electrical setups.

    Installation is straightforward thanks to its compatibility with standard DIN rails (TS-35/7.5 or 15), enabling quick and secure mounting in industrial enclosures. To ensure safe and reliable operation, the metal housing must be properly grounded. Correct wiring is essential: always follow the labeled terminal markings for input and output connections, and firmly tighten all terminal screws to prevent overheating caused by loose contacts.

    Each unit undergoes a rigorous 100% full-load burn-in test before leaving the factory, verifying its reliability under real-world conditions. It also includes essential protections against short circuits, overloads, and over-voltage events, safeguarding both the power supply and connected equipment. An integrated LED indicator provides clear visual confirmation of operation status at a glance.

    Suitable for indoor industrial environments, the DR Series should be installed in clean, dry locations away from excessive dust, moisture, or corrosive gases. For harsher conditions such as outdoor or wet environments, we recommend selecting a model with an IP65 or higher ingress protection rating.

    Backed by a 3-year warranty, this DIN rail power supply offers a trusted combination of durability, safety, and ease of use, making it a solid choice for professionals seeking reliable power in industrial settings.

    Features

    ●High efficiency,high reliability,small size
    ●Working Temp-25℃~70℃
    ●Can be installed on DIN rail TS-35/7.5 or15 
    ●100% full load burn-in test
    ●Protections:short circuit/over load/over voltage
    ●With boot display(LED Light Emitting Diode) 
    ●3 year warranty

    HDR-30

     HDR-30(1).jpg

    Model

    HDR-30

    Input voltage range

    AC85-264VAC or DC 125-373VDC

    DC Output

    3.3V 3.0A

    5.0V 3.0A

    12V 2.0A

    24V 1.5A

    48V 0.8A

    Ripple&Noise

    80mv

    80mv

    120mv

    120mv

    120mv

    Efficiency

    75%

    78%

    81%

    83%

    85%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.24Kg/50pcs/12.5Kg

    Dimension

    78*93*56mm(L*W*H)

    HDR-30.jpgHDR-45

     HDR-45.jpg

    Model

    HDR-45

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    3.3V 5.0A

    5.0V 5.0A

    12V 3.5A

    24V 2.0A

    48V 1.0A

    Ripple&Noise

    80mv

    80mv

    120mv

    120mv

    120mv

    Efficiency

    76%

    80%

    81%

    84%

    86%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.24Kg/50pcs/12.5Kg

    Dimension

    78*93*56mm(L*W*H)

    HDR-45.jpgHDR-60

     HDR-60.jpg

    Model

    HDR-60

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    3.3V 7.0A

    5.0V 6.5A

    12V 4.5A

    24V 2.5A

    48V 1.3A

    Ripple&Noise

    80mv

    80mv

    120mv

    150mv

    150mv

    Efficiency

    76%

    80%

    82%

    84%

    86%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.25Kg/50pcs/13.2Kg

    Dimension

    78*93*56mm(L*W*H)

    HDR-60.jpg

    HDR-15S

     HDR-15(1).jpg

    Model

    HDR-15S

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    5V 2.4A

    12V 1.25A

    24V 0.63A

    Ripple&Noise

    80mv

    120mv

    150mv

    Efficiency

    80%

    85%

    86%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    /

    Packing

    0.074Kg/160pcs/12.9Kg

    Dimension

    17.5*90*54.5mm(L*W*H)

    HDR-15S.jpg

    HDR-30S

     HDR-30S.jpg

    Model

    HDR-30S

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    5V 3.0A

    12V 2.0A

    24V 1.5A

    Ripple&Noise

    80mv

    120mv

    150mv

    Efficiency

    80%

    86%

    87%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    /

    Packing

    0.13Kg/96pcs/14.2Kg

    Dimension

    35*90*54.5mm(L*W*H)

    HDR-30S.jpgHDR-60S

     HDR-60(1).jpg

    Model

    HDR-60S

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    5V 6.5A

    12V 4.5A

    24V 2.5A

    Ripple&Noise

    80mv

    120mv

    150mv

    Efficiency

    80%

    86%

    87%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    /

    Packing

    0.19Kg/60pcs/13Kg

    Dimension

    52.5*90*54.5mm(L*W*H)

    HDR-60S.jpgHDR-100S

     HDR-100(1).jpg

    Model

    HDR-100S

    Input voltage range

    AC 180-264VAC or DC 254-373VDC

    DC Output

    12V 7.1A

    24V 4.2A

    Ripple&Noise

    120mv

    150mv

    Efficiency

    86%

    87%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.27Kg/48pcs/13.7Kg

    Dimension

    70*90*54.5mm(L*W*H)

    HDR-100S.jpgHDR-75

     HDR-75(1).jpg

    Model

    HDR-75

    Input voltage range

    AC85-264VAC or DC 125-373VDC

    DC Output

    12V 6.3A

    24V 3.2A

    48V 1.6A

    Ripple&Noise

    100mv

    120mv

    200mv

    Efficiency

    81%

    82%

    84%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.56Kg/27pcs/15.8Kg

    Dimension

    55.5*125.2*100mm(L*W*H)

    HDR-75.jpgHDR-120

     HDR-120(1).jpg

    Model

    HDR-120

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    12V 10A

    24V 5.0A

    48V 2.5A

    Ripple&Noise

    100mv

    120mv

    200mv

    Efficiency

    81%

    83%

    84%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.65Kg/24pcs/16.4Kg

    Dimension

    65.5*125.2*100mm(L*W*H)

    HDR-120.jpgHDR-240

     HDR-240.jpg

    Model

    HDR-240

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    12V 16.5A

    24V 10A

    48V 5.0A

    Ripple &Noise

    80mv

    80mv

    150mv

    Efficiency

    81%

    84%

    85%

    Over Load

    110%~150% current limiting,recovers automatically after fault condition is removed.

    Over Voltage

    115%~135% shut down o/p voltage,re-power on to recover

    Packing

    1.02Kg/12pcs/13Kg

    Dimension

    125*125.2*100mm(L*W*H)

    HDR-240.jpgHDR-480

     HDR-480.jpg

    Model

    HDR-480

    Input voltage range

    AC 180-264VAC or DC 254-373VDC

    DC Output

    24V 20A

    48V 10A

    Ripple &Noise

    120mv

    120mv

    Efficiency

    87%

    89%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% shut down o/p voltage,re-power on to

    recover

    Packing

    2.4Kg/6pcs/15Kg

    Dimension

    227*125.2*100mm(L*W*H)

    HDR-480.jpgNDR-75

     NDR-75(1).jpg

    Model

    NDR-75

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    12V 6.3A

    24V 3.2A

    48V 1.6A

    Ripple&Noise

    100mv

    120mv

    200mv

    Efficiency

    84%

    86%

    87%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.40Kg/46pcs/19Kg

    Dimension

    32*125.2*102mm(L*W*H)

    NDR-75.jpg

    NDR-120

     NDR-120.jpg

    Model

    NDR-120

    Input voltage range

    AC 85-264VAC or DC 125-373VDC

    DC Output

    12V 10A

    24V 5.0A

    48V 2.5A

    Ripple&Noise

    100mv

    120mv

    200mv

    Efficiency

    84%

    86%

    87%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% hiccup mode,recovers automatically after fault condition is removed

    Packing

    0.50Kg/30pcs/15.5Kg

    Dimension

    40*125.2*113.5mm(L*W*H)

    NDR-120.jpgNDR-240

     NDR-240.jpg

    Model

    NDR-240

    Input voltage range

    AC 180-264VAC or DC 254-373VDC

    DC Output

    24V 10A

    48V 5A

    Ripple &Noise

    120mv

    120mv

    Efficiency

    87%

    89%

    Over Load

    110%~150% hiccup mode,recovers automatically after fault condition is removed

    Over Voltage

    115%~135% shut down o/p voltage,re-power on to recover

    Packing

    0.72Kg/18pcs/13.7Kg

    Dimension

    63*125.2*113.5mm(L*W*H)

    NDR-240.jpgNDR-480              

     NDR-480.jpg

    Model

    NDR-480

    Input voltage range

    AC 180-264VAC or DC 254-373VDC

    DC Output

    24V20A

    48V10A

    Ripple &Noise

    120mv

    120mv

    Efficiency

    87%

    89%

    Over Load

    110%~150% current limiting,recover automatically after fault condition is removed.

    Over Voltage

    115%~135% shut down o/p voltage,re-power on to recover

    Packing

    0.95Kg/16pcs/15.8Kg

    Dimension

    85.5*125.2*128.5mm(L*W*H)

    NDR-480.jpg