HDR black series SMPS,Single Output Industrial, DIN Rail Power Supply
Product Model Meaning

Product Introduction
Built to meet the needs of modern industrial applications, the DR Series power supply offers a dependable and efficient solution for delivering stable DC power. Its compact design saves valuable panel space while maintaining high reliability, making it ideal for integration into control cabinets, machinery, and automation systems.
Engineered for performance and longevity, this power supply operates efficiently across a broad ambient temperature range of -25°C to +70°C. For optimal service life, we recommend maintaining the operational load between 20% and 80% of its rated capacity, and ensuring at least 5 cm of clearance around the unit to support effective heat dissipation. It accepts a wide input voltage range—typically AC 100-240V—allowing flexible deployment across different regions and electrical setups.
Installation is straightforward thanks to its compatibility with standard DIN rails (TS-35/7.5 or 15), enabling quick and secure mounting in industrial enclosures. To ensure safe and reliable operation, the metal housing must be properly grounded. Correct wiring is essential: always follow the labeled terminal markings for input and output connections, and firmly tighten all terminal screws to prevent overheating caused by loose contacts.
Each unit undergoes a rigorous 100% full-load burn-in test before leaving the factory, verifying its reliability under real-world conditions. It also includes essential protections against short circuits, overloads, and over-voltage events, safeguarding both the power supply and connected equipment. An integrated LED indicator provides clear visual confirmation of operation status at a glance.
Suitable for indoor industrial environments, the DR Series should be installed in clean, dry locations away from excessive dust, moisture, or corrosive gases. For harsher conditions such as outdoor or wet environments, we recommend selecting a model with an IP65 or higher ingress protection rating.
Backed by a 3-year warranty, this DIN rail power supply offers a trusted combination of durability, safety, and ease of use, making it a solid choice for professionals seeking reliable power in industrial settings.
Features
●High efficiency,high reliability,small size
●Working Temp-25℃~70℃
●Can be installed on DIN rail TS-35/7.5 or15
●100% full load burn-in test
●Protections:short circuit/over load/over voltage
●With boot display(LED Light Emitting Diode)
●3 year warranty
HDR-30
|
|
Model |
HDR-30 |
||||
|
Input voltage range |
AC85-264VAC or DC 125-373VDC |
|||||
|
DC Output |
3.3V 3.0A |
5.0V 3.0A |
12V 2.0A |
24V 1.5A |
48V 0.8A |
|
|
Ripple&Noise |
80mv |
80mv |
120mv |
120mv |
120mv |
|
|
Efficiency |
75% |
78% |
81% |
83% |
85% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
|||||
|
Packing |
0.24Kg/50pcs/12.5Kg |
|||||
|
Dimension |
78*93*56mm(L*W*H) |
|||||
HDR-45
|
|
Model |
HDR-45 |
||||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||||
|
DC Output |
3.3V 5.0A |
5.0V 5.0A |
12V 3.5A |
24V 2.0A |
48V 1.0A |
|
|
Ripple&Noise |
80mv |
80mv |
120mv |
120mv |
120mv |
|
|
Efficiency |
76% |
80% |
81% |
84% |
86% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
|||||
|
Packing |
0.24Kg/50pcs/12.5Kg |
|||||
|
Dimension |
78*93*56mm(L*W*H) |
|||||
HDR-60
|
|
Model |
HDR-60 |
||||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||||
|
DC Output |
3.3V 7.0A |
5.0V 6.5A |
12V 4.5A |
24V 2.5A |
48V 1.3A |
|
|
Ripple&Noise |
80mv |
80mv |
120mv |
150mv |
150mv |
|
|
Efficiency |
76% |
80% |
82% |
84% |
86% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
|||||
|
Packing |
0.25Kg/50pcs/13.2Kg |
|||||
|
Dimension |
78*93*56mm(L*W*H) |
|||||

HDR-15S
|
|
Model |
HDR-15S |
||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||
|
DC Output |
5V 2.4A |
12V 1.25A |
24V 0.63A |
|
|
Ripple&Noise |
80mv |
120mv |
150mv |
|
|
Efficiency |
80% |
85% |
86% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Over Voltage |
/ |
|||
|
Packing |
0.074Kg/160pcs/12.9Kg |
|||
|
Dimension |
17.5*90*54.5mm(L*W*H) |
|||

HDR-30S
|
|
Model |
HDR-30S |
||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||
|
DC Output |
5V 3.0A |
12V 2.0A |
24V 1.5A |
|
|
Ripple&Noise |
80mv |
120mv |
150mv |
|
|
Efficiency |
80% |
86% |
87% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Over Voltage |
/ |
|||
|
Packing |
0.13Kg/96pcs/14.2Kg |
|||
|
Dimension |
35*90*54.5mm(L*W*H) |
|||
HDR-60S
|
|
Model |
HDR-60S |
||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||
|
DC Output |
5V 6.5A |
12V 4.5A |
24V 2.5A |
|
|
Ripple&Noise |
80mv |
120mv |
150mv |
|
|
Efficiency |
80% |
86% |
87% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Over Voltage |
/ |
|||
|
Packing |
0.19Kg/60pcs/13Kg |
|||
|
Dimension |
52.5*90*54.5mm(L*W*H) |
|||
HDR-100S
|
|
Model |
HDR-100S |
|
|
Input voltage range |
AC 180-264VAC or DC 254-373VDC |
||
|
DC Output |
12V 7.1A |
24V 4.2A |
|
|
Ripple&Noise |
120mv |
150mv |
|
|
Efficiency |
86% |
87% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
||
|
Packing |
0.27Kg/48pcs/13.7Kg |
||
|
Dimension |
70*90*54.5mm(L*W*H) |
||
HDR-75
|
|
Model |
HDR-75 |
||
|
Input voltage range |
AC85-264VAC or DC 125-373VDC |
|||
|
DC Output |
12V 6.3A |
24V 3.2A |
48V 1.6A |
|
|
Ripple&Noise |
100mv |
120mv |
200mv |
|
|
Efficiency |
81% |
82% |
84% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Packing |
0.56Kg/27pcs/15.8Kg |
|||
|
Dimension |
55.5*125.2*100mm(L*W*H) |
|||
HDR-120
|
|
Model |
HDR-120 |
||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||
|
DC Output |
12V 10A |
24V 5.0A |
48V 2.5A |
|
|
Ripple&Noise |
100mv |
120mv |
200mv |
|
|
Efficiency |
81% |
83% |
84% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Packing |
0.65Kg/24pcs/16.4Kg |
|||
|
Dimension |
65.5*125.2*100mm(L*W*H) |
|||
HDR-240
|
|
Model |
HDR-240 |
||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||
|
DC Output |
12V 16.5A |
24V 10A |
48V 5.0A |
|
|
Ripple &Noise |
80mv |
80mv |
150mv |
|
|
Efficiency |
81% |
84% |
85% |
|
|
Over Load |
110%~150% current limiting,recovers automatically after fault condition is removed. |
|||
|
Over Voltage |
115%~135% shut down o/p voltage,re-power on to recover |
|||
|
Packing |
1.02Kg/12pcs/13Kg |
|||
|
Dimension |
125*125.2*100mm(L*W*H) |
|||
HDR-480
|
|
Model |
HDR-480 |
|
|
Input voltage range |
AC 180-264VAC or DC 254-373VDC |
||
|
DC Output |
24V 20A |
48V 10A |
|
|
Ripple &Noise |
120mv |
120mv |
|
|
Efficiency |
87% |
89% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
||
|
Over Voltage |
115%~135% shut down o/p voltage,re-power on to recover |
||
|
Packing |
2.4Kg/6pcs/15Kg |
||
|
Dimension |
227*125.2*100mm(L*W*H) |
||
NDR-75
|
|
Model |
NDR-75 |
||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||
|
DC Output |
12V 6.3A |
24V 3.2A |
48V 1.6A |
|
|
Ripple&Noise |
100mv |
120mv |
200mv |
|
|
Efficiency |
84% |
86% |
87% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Packing |
0.40Kg/46pcs/19Kg |
|||
|
Dimension |
32*125.2*102mm(L*W*H) |
|||

NDR-120
|
|
Model |
NDR-120 |
||
|
Input voltage range |
AC 85-264VAC or DC 125-373VDC |
|||
|
DC Output |
12V 10A |
24V 5.0A |
48V 2.5A |
|
|
Ripple&Noise |
100mv |
120mv |
200mv |
|
|
Efficiency |
84% |
86% |
87% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Over Voltage |
115%~135% hiccup mode,recovers automatically after fault condition is removed |
|||
|
Packing |
0.50Kg/30pcs/15.5Kg |
|||
|
Dimension |
40*125.2*113.5mm(L*W*H) |
|||
NDR-240
|
|
Model |
NDR-240 |
|
|
Input voltage range |
AC 180-264VAC or DC 254-373VDC |
||
|
DC Output |
24V 10A |
48V 5A |
|
|
Ripple &Noise |
120mv |
120mv |
|
|
Efficiency |
87% |
89% |
|
|
Over Load |
110%~150% hiccup mode,recovers automatically after fault condition is removed |
||
|
Over Voltage |
115%~135% shut down o/p voltage,re-power on to recover |
||
|
Packing |
0.72Kg/18pcs/13.7Kg |
||
|
Dimension |
63*125.2*113.5mm(L*W*H) |
||
NDR-480
|
|
Model |
NDR-480 |
|
|
Input voltage range |
AC 180-264VAC or DC 254-373VDC |
||
|
DC Output |
24V20A |
48V10A |
|
|
Ripple &Noise |
120mv |
120mv |
|
|
Efficiency |
87% |
89% |
|
|
Over Load |
110%~150% current limiting,recover automatically after fault condition is removed. |
||
|
Over Voltage |
115%~135% shut down o/p voltage,re-power on to recover |
||
|
Packing |
0.95Kg/16pcs/15.8Kg |
||
|
Dimension |
85.5*125.2*128.5mm(L*W*H) |
||


JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits