0102030405
FN3‑12 Indoor High‑Voltage Load Switch
Main Technical Parameters
1. The basic technical parameters of the load switch shall comply with the following table:
| Model | Rated Voltage (kV) | Maximum Operating Voltage (kV) | Rated Current (A) | Rated Short-Time Withstand Current (kA) | Rated Thermal Withstand Current (kA/s) |
|---|---|---|---|---|---|
| FN3-12 | 12 | 12 | 400 | 25 | 10/2 |
2. The fuse models and technical parameters equipped with the load switch shall comply with the following table:
| Model | Rated Voltage (kV) | Rated Current (A) | Maximum Breaking Current (Effective Value) (kA) | Maximum Breaking Capacity (kVA) | Current Limiting Fuse Breaking Current (kA) |
|---|---|---|---|---|---|
| RN3-3 | 3 | 10–50 | 40 | 200 | 24.5 |
| 75–100 | 24.5 | ||||
| 200 | 35 | ||||
| RN3-6 | 6 | 10–50 | 20 | 200 | 14 |
| 75 | 14 | ||||
| 100 | 19 | ||||
| 200 | 25 | ||||
| RN3-10 | 12 | 10–50 | 12 | 200 | 8.6 |
| 72 | 8.6 | ||||
| 100–500 | 15.5 |

Part 1
- Bell crank arm
- Frame
- Upper insulator
- Main static contact
- Arc moving contact
- Switch blade
- Insulating pull rod
- Lower contact base
- Lower insulator
- Fuse
Part 2
- Socket
- Frame
- Fuse tube
- Load switch main body

JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits