FKN12‑12A Indoor High‑Voltage Load Switch‑Fuse Combination Unit
Main Technical Parameters
| No. | Item | Unit | Parameter | |
|---|---|---|---|---|
| FKN12A‑12D | FZN25‑12D/T630‑20 | |||
| 1 | Rated voltage | kV | 12 | 12 |
| 2 | Rated frequency | Hz | 50 | 50 |
| 3 | Rated current | A | 630 | 125 |
| 4 | Rated insulation level 1‑min power‑frequency withstand voltage to earth / between phases isolating break Rated lightning impulse withstand voltage to earth / between phases isolating break |
kV kV kV kV |
42 48 75 85 |
42 48 75 85 |
| 5 | Rated short‑time withstand current Load switch Earthing switch |
kA kA |
20 20 |
‑ 20 |
| 6 | Rated short‑circuit duration Load switch Earthing switch |
s s |
4 2 |
‑ 2 |
| 7 | Rated short‑circuit making current (peak value) | kA | 50 | ‑ |
| 8 | Rated breaking current Active load breaking current Ring‑network breaking current 5% active load breaking current Cable charging current |
A A A A |
630 630 31.5 10 |
‑ ‑ ‑ ‑ |
| 9 | Rated breaking capacity of no‑load transformer | kVA | 1250 | 1250 |
| 10 | Rated short‑circuit breaking current (for limiting fuse) | kA | ‑ | 31.5 |
| 11 | Rated transfer current | A | ‑ | 1200 |
| 12 | Mechanical endurance | times | 2000 | 2000 |
| 13 | Energy output of striker | J | ‑ | 1+0.5 |
Mechanical Dimension & Timing Parameters
| No. | Item | Unit | Parameter |
|---|---|---|---|
| 1 | Break opening distance | mm | ≥175 |
| 2 | Phase‑to‑phase centre distance | mm | 210±2 |
| 3 | Phase‑to‑phase air clearance | mm | ≥125 |
| 4 | Travel | mm | 210±4 |
| 5 | Over‑travel | mm | ≥40 |
| 6 | 3‑phase closing asynchronous time | ms | ≤10 |
| 7 | 3‑phase opening asynchronous time | ms | ≤5 |
| 8 | Inherent opening‑time of tripping device | ms | 40‑65 |
| 9 | Main‑circuit resistance | μΩ | ≤130 |







JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits