0102030405
GW4A-40.5kV Outdoor High Voltage Isolating Switch
Main Technical Parameters
| Item | Unit | GW4‑12 | GW4‑40.5 | GW4‑72.5 | GW4‑126 | GW4‑126G | GW4‑145 |
|---|---|---|---|---|---|---|---|
| Rated Voltage | kV | 12 | 40.5 | 72.5 | 126 | 126 | 145 |
| Rated Current | A | 200 400 630 1000 250 |
630 1000 2000 2500 |
630 1250 2000 2500 |
630 1250 2000 2500 |
530 1250 |
530 1250 2000 2500 |
| Rated Short‑time Withstand Current (r.m.s.) | kA | 16 20 25 |
20 31.5 40(46) |
20 31.5 40(46) |
20 31.5 40(46) |
20 31.5 |
20 31.5 40(46) |
| Rated Peak Withstand Current (r.m.s.) | kA | 40 50 63 |
50 80 100(104) |
50 80 100(104) |
50 80 100(104) |
50 80 |
50 80 100(104) |
| 1min Power‑frequency Withstand Voltage (r.m.s.) To Earth | kV | 42 | 80 | 140 | 185 | 185 | 275 |
| Break | kV | 48 | 90 | 160 | 210(265) | 210 | 315 |
| Lightning Impulse Withstand Voltage (peak) To Earth | kV | 75 | 185 | 325 | 450(550) | 450 | 650 |
| Break | kV | 85 | 215 | 375 | 520(530) | 550 | 750 |
| Terminal Horizontal Tensile Force | N | 250 | 490(735) | 735 | 735 | 735 | 980 |
| Unit Weight | Kg | 60 | 80 | 200 | 240 | 240 | 300 |
| Remarks | ‑ | ‑ | ‑ | ‑ | ‑ | For altitude 2000m | Applicable for 110kV, altitude 4000 |
Outline and Installation Dimension Drawing


JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits