HHT10 Series Bar-type Vertical Fuse Switch Disconnector 160A to 630A - China Factory Suppliers, Rated 690V
Meaning of Product Model
Normal Working and Installation Conditions
The ambient air temperature shall not exceed +40℃ and not be lower than -5℃.
The altitude of the installation site shall not exceed 2000m.
When the maximum temperature is +40℃, relative humidity does not exceed 50%. Reaching up to 90% at 20℃ is allowable. Occasional condensation due to temperature changes requires special measures.
The pollution level of the surrounding environment is level 3.
Must be installed without significant shaking, vibration, rain, or snow. Free from explosive hazardous media, corrosive gas, and insulation-damaging dust.
Structure Characteristics
The switch is composed of a base, contacts, cover, operating handle, arc extinguishing device, etc. The base is made of unsaturated polyester molded plastic, and the rest are pressed with arc resistant plastic. The fuse installed on the cover serves as the moving contact. The handle rotates in a fan-shaped motion along the fulcrum on the base, and the cover is connected to the fuse for opening and closing. The base is equipped with an arc extinguishing chamber to ensure the segmented ability of the switch. This product has a simple structure that is easy to disassemble and assemble.
The advantages of strong arc extinguishing ability and beautiful appearance. There are two installation methods: screw fixed installation and hook fixed installation. Fixed installation with hooks, the busbar does not require punching, making installation more convenient, flexible, and reliable.
A 3-pole strip fuse holder installed on the bus track. It integrates three vertically arranged single pole fuse holders, with one contact (feed contact) of each phase connected to one phase, and other contacts (output contact) equipped with wire connection devices.
The carrier for the live parts of the fuse holder is made of sturdy fiberglass reinforced polyester material. The silver plated fuse contacts are combined with the tin plated lead plate to ensure low energy consumption of the product; High power acceptance and low temperature rise.
There are two installation methods: screw fixed installation and hook fixed installation.
Fixed installation with hooks, the busbar does not require punching, making installation more convenient, flexible, and reliable.
Main Technical Parameters
Relationship between switches and fuses
| Agreed heating current Ith | Matching fuse size | Rated current of fuse (A) |
|---|---|---|
| 160 | NT00、NH00 | 10、16、25、32、40、50、63、80、100、125、160 |
| 250 | NT1、NH1 | 63、80、100、125、160、200、250 |
| 400 | NT2、NH2 | 160、200、250、315、400 |
| 630 | NT3、NH3 | 250、315、400、500、630 |
Main technical parameters of switches
| Current Rating (A) | 160 | 250 | 400 | 630 | |||||||||||
| With fuse |
Rated working voltage | Ue | V | AC400 | AC500 | AC690 | AC400 | AC500 | AC690 | AC400 | AC500 | AC690 | AC400 | AC500 | AC690 |
| Rated working current | le | A | 160 | 125 | 100 | 250 | 250 | 200 | 400 | 400 | 315 | 630 | 630 | 500 | |
| Agreed heating current | lth | A | 160 | 125 | 100 | 250 | 250 | 200 | 400 | 400 | 315 | 630 | 630 | 500 | |
| Utilization category | AC-23B | AC-22B | AC-21B | AC-23B | AC-22B | AC-21B | AC-23B | AC-22B | AC-21B | AC-23B | AC-22B | AC-21B | |||
| Rated limiting breaking current | lq | kA | 50 | 100 | 100 | 50 | 100 | 100 | 50 | 100 | 100 | 50 | |||
| Rated insulation voltage | Ui | V | 1000 | 1000 | 1000 | 1000 | |||||||||
| Rated impulse withstand voltage | Uimp | kV | 12 | 12 | 12 | 12 | |||||||||
| Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | ||||||||||
| Electrical life | Time | 200 | 200 | 200 | 200 | ||||||||||
| With isolation knife |
Rated operational voltage | Ue | V | / | AC500 | AC500 | AC500 | ||||||||
| Rated working current | le | A | / | 250 | 400 | 630 | |||||||||
| Agreed heating current | lth | A | / | 250 | 400 | 630 | |||||||||
| Utilization category | / | AC-23B | AC-23B | AC-23B | |||||||||||
| Short time withstand current | lcw | KA | / | 12 | 12 | 12 | |||||||||
| Rated insulation voltage | Ui | V | / | 1000 | 1000 | 1000 | |||||||||
| Rated impulse withstand voltage | Uimp | kV | / | 12 | 12 | 12 | |||||||||
| Rated frequency | Hz | / | 50/60 | 50/60 | 50/60 | ||||||||||
| Electrical life | Time | / | 200 | 200 | 200 | ||||||||||
| Mechanism | Mechanical lifespan | Time | 1400 | 1400 | 800 | 800 | |||||||||
| Distance between busbars | mm | 185 | 185 | 185 | 185 | ||||||||||
| IP Grade |
Front | Open | IP20 | IP20 | IP20 | IP20 | |||||||||
| Closing | IP30 | IP30 | IP30 | IP30 | |||||||||||
| Working conditions |
Way of working | Work-conserving | |||||||||||||
| Manipulate | Hand shank | ||||||||||||||
| Installation | Perpendicular | ||||||||||||||
| Pollution degree | 3 | ||||||||||||||
| Overvoltage level | I | IV | |||||||||||||
Installation Precautions
1. The contact parameters of the switch have been set by the manufacturer and cannot be adjusted freely during use.
2. During the connection process between the busbar and the product, it is necessary to ensure that the distance between the busbar holes is consistent with the product wiring holes to avoid product damage caused by external forces.
Ordering Notice
Customers must indicate the product name, model, rated current, number of poles, and quantity, for example: HHT10-400/3F (with fuse 315A).
Note: The specifications and external dimensions may change due to product improvements without prior notice, and the actual product shall prevail.

JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits