HR6 Series Fuse‑Switch Disconnector 3P 160‑630A Manual Load Isolation Switch With Fuse Protection
Product Model Meaning

Normal Working and Installation Conditions
1.The ambient air temperature shall not exceed +40℃ and not be lower than -5℃.
2.The altitude of the installation site shall not exceed 2000m.
3.Humidity: When the maximum temperature is +40℃ , the relative humidity of the air does not exceed 50%. Higher relative humidity can be allowed at lower temperatures, such as reaching 90% at 20℃. Special measures should be taken for occasional condensation caused by temperature changes.
4.The pollution level of the surrounding environment is level 3.
5.The switch should be installed in a place without significant shaking, impact vibration, and invasion of rain and snow. At the same time, the installation location should be free of explosive hazardous media, and there should be no gas or dust in the media that can corrode metals and damage insulation.
Structural Feature
The switch is composed of a base, a cover, and an arc extinguishing chamber, all made of arc resistant plastic and is a fully plastic structure. The static contact is directly installed on the base, making the disassembly and assembly of the arc extinguishing chamber convenient.
Each arc extinguishing chamber has two parts: an inner chamber and an outer chamber. Multiple metal arc extinguishing grids are used to enhance the arc extinguishing ability and improve the contact life. The NT type fuse link is installed inside the cover, which can rotate in a fan-shaped manner and has a large electrical isolation distance to meet the requirements of the isolation switch.
The cover can be easily removed from the base, making installation and replacement of the fuse link very convenient. There are two sets of installation holes on the base, which can meet the requirements for installation in various switchgear cabinets and panels.
On both sides of the switch, auxiliary contacts can be installed as needed to send signals indicating the opening and closing status of the switch. The direct isolation knife type can be used as a knife switch. The hanging type installation can be directly installed in the busbar system without drilling, meeting the requirements of the national grid. The hanging type product also provides upper and lower input and output structures, namely upper wiring type (upper incoming line) and lower wiring type (lower outgoing line)
Main Technical Parameters
Matching relationship between switches and fuses
|
Conventional |
Model of |
Rated operational |
Rated current of fuse link (A) |
|
160 |
NT00、RT16-00 |
AC-23B 400 |
2、4、6、10、16、20、25、32、40、50、63、80、100、125、160 |
|
NH00 |
AC-23B 690 |
2、4、6、10、16、20、25、32、40、50、63、80、100 |
|
|
250 |
NT1、RT16-1 |
AC-23B 400 |
40、50、63、80、100、125、160、200、225、250 |
|
NH1 |
AC-23B 690 |
40、50、63、80、100、125、160、200 |
|
|
400 |
NT2、RT16-2 |
AC-23B 400 |
160、200、250、300、315、350、400 |
|
NH2 |
AC-23B 690 |
160、200、250、300、315 |
|
|
630 |
NT3、RT16-3 |
AC-23B 400 |
315、400、500、630 |
|
NH3 |
AC-23B 690 |
315、400、500 |
|
|
800 |
CRT3 |
AC-23B 400 |
800 |
|
1000 |
NT4、RT17 |
AC-23B 400 |
800、1000 |
|
NH4 |
AC-23B 690 |
800 |
Main technical parameters of the switch
|
Model Specifications |
HR6-160 |
HR6-250 |
HR6-400 |
HR6-630 |
HR6-800 |
HR6-1000 |
||
|
Conventional Thermal Current(A) |
160 |
250 |
400 |
630 |
800 |
1000 |
||
|
Rated Insulation Voltage Ui(V) |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
||
|
Rated Impulse Withstand Voltage(kV) |
12 |
12 |
12 |
12 |
12 |
12 |
||
|
Rated Working Current(A) |
500V |
160 |
250 |
400 |
630 |
800 |
1000 |
|
|
690V |
100 |
200 |
315 |
425 |
630 |
800 |
||
|
Rated making |
AC500V,AC-22B |
Connect |
1600 |
2500 |
4000 |
6300 |
8000 |
10000 |
|
AC500V,AC-22B |
Breaking |
1280 |
2000 |
3200 |
5040 |
6400 |
8000 |
|
|
Mechanical Life (Time) |
1400 |
800 |
800 |
800 |
800 |
800 |
||
|
Electrical Life (Time) |
200 |
200 |
200 |
200 |
200 |
200 |
||
|
Operating Force (N) |
≤400 |
≤400 |
≤400 |
≤400 |
≤400 |
≤400 |
||
|
Rated Conditional Short-circuit |
50 |
50 |
100 |
100/50 |
100 |
100 |
||
|
Usage Category |
AC-23B |
AC-23B |
AC-23B |
AC-23B |
AC-23B |
AC-23B |
||
|
Pollution Degree |
3 |
3 |
3 |
3 |
3 |
3 |
||
|
Degrees of Protection Provided by Enclosure |
Ⅲ |
Ⅲ |
Ⅲ |
Ⅲ |
Ⅲ |
Ⅲ |
||
Installation Precautions
1.The contact parameters of the switch have been set by the manufacturer and cannot be adjusted freely during use.
2.During the connection process between the busbar and the product, it is necessary to ensure that the distance between the busbar row holes is consistent with the product wiring holes to avoid product damage caused by exteral forces.
Ordering Information
The customer must indicate the product name, model, rated current, number of poles, and quantity, etc. Example 1:HR6-400/30 690V (with fuse:400A) Quantity:10 units; Example 2:HR6-630/31G(upper incoming line) 690V (with fuse:630A) Quantity:10 units
Note: The specifications and dimensions are subject to change due to product improvements without prior notice, and the actual product shall prevail.