JDZ9-20 Type Voltage Transformer - China Suppliers & Factory for 20kV AC Power Systems and Metering Solutions
Model and Its Meaning
Overview
In the field of electrical engineering, the importance of reliable and efficient power measurement equipment cannot be overstated. Among these devices, indoor voltage transformers are key components in medium and high voltage power systems. Our 15-35kV indoor voltage transformers are high-performance, highly reliable power measurement devices designed to meet the demands of modern power infrastructure.
The primary function of indoor voltage transformers is to provide precise voltage measurements, which are crucial for power system monitoring and protection. Our 15-35kV indoor voltage transformers excel in this regard, offering high-precision measurement capabilities. These transformers feature excellent linearity and low phase error, ensuring accurate and reliable voltage readings. This precision is crucial for effective power system monitoring and protection, as even small discrepancies in voltage measurements can lead to serious operational issues.
Normal Service Conditions
📍Installation Site: Indoor
🌡️Ambient Temperature: Maximum air temperature 40℃; The minimum temperature is -5℃. The daily average temperature does not exceed 30℃.
🌤️Atmospheric Conditions: There is no severe pollution in the atmosphere.
Technical Parameters
Product |
Rated Voltage Ratio (kV) |
Accuracy Level or a Combination of Accuracy Levels |
Rated Output (VA) |
Extreme Output (VA) |
Rated Insulation Level (kV) |
| JDZ9-20 | 20/0.1 20/0.1/0.1 |
0.2 | 15 | 500 | 24/65/125 |
| 0.5 | 30 | ||||
| 20/√3/0.1/√3/0.1/3 20/√3/0.1/√3/0.1/√3/0.1/3 |
0.2 | 15 | 2*300 | ||
| 0.5 | 50 | ||||
| 3P | 100 |
Structure and Characteristics
- Pillar-type design with a fully enclosed epoxy resin casting process.
- Excellent resistance to contamination and moisture — suitable for use in tropical regions.
- Requires no special maintenance; only regular surface cleaning is needed.
- Secondary terminals equipped with a terminal box with holes on the front and side for safe and reliable wiring.
- Baseplate equipped with a grounding bolt and six mounting holes for easy installation.