Zhejiang Donghua Electrical Appliance Co., Ltd.
Leave Your Message
Products Categories
Featured Products

JDZJ(18)-3,6,10 Voltage Transformer | 3‑10kV Indoor Cast Resin VT

The JDZJ(18)-3, 6, and 10 type voltage transformers are suitable for AC power systems with a rated frequency of 50Hz or 60Hz and a rated voltage of 3-10kV, and are used for electric energy metering, voltage measurement, and relay protection.
The product execution standards are GB20840.1-2010 and GB20840.3-2013.

    Model and its meaning

    jdzj-18-3-6-10-1.jpg

    Summarize

    Beyond their core functions, voltage transformers also facilitate the implementation of automation and remote monitoring systems. By combining voltage transformers with advanced monitoring technologies, operators can remotely collect data, enabling real-time analysis and decision-making. This capability not only simplifies operations but also reduces the costs associated with high-voltage measurement equipment. Furthermore, some voltage transformers offer multiple functions, including additional features such as frequency and phase measurement. This integration provides a comprehensive monitoring solution, offering valuable insights into power system performance.

    Normal service condition

    Installation site: Indoor

    Ambient temperature: The maximum temperature is 40℃ , the minimum temperature is -5℃ , and the daily average temperature does not exceed 30℃ .

    Atmospheric conditions: Ensure that there is no serious pollution in the atmosphere to avoid affecting the insulation performance and working stability of the equipment.

    When the above conditions are met, the voltage transformer can operate normally and safely.

    Technical parameter

    Product
    model

    Rated voltage ratio

    Accuracy
    level

    Rated
    output(VA)

    Extreme
    output(VA)

    Rated insulation
    level(KV)

    JDZJ(18)-3

    3/√ 3/0.1/√3/0.1/3

    0.2/3P

    15/50

    200

    3.6/25/40

    0.5/3P

    30/50

    JDZJ(18)-6

    6/√ 3/0.1/√3/0.1/3

    0.2/3P

    15/50

    200

    7.2/32/60

    0.5/3P

    30/50

    JDZJ(18)-10

    10/√3/0.1/√3/0.1/3

    0.2/3P

    15/50

    200

    12/42/75

    0.5/3P

    30/50

    JDZJ(18)-3

    3/√ 3/0.1/√3/0.1/3

    0.2/3P

    20/50

    200

    3.6/25/40

    0.2/0.5/3P

    15/15/50

    JDZJ(18)-6

    6/√ 3/0.1/√3/0.1/3

    0.2/3P

    20/50

    200

    7.2/32/60

    0.2/0.5/3P

    15/15/50

    JDZJ(18)-10

    10/√3/0.1/√3/0.1/3

    0.2/3P

    20/50

    200

    12/42/75

    0.2/0.5/3P

    15/15/50

    Structure and characteristics

    This series of voltage transformers adopt a pillar structure and are fully enclosed with epoxy resin by epoxy casting. They are resistant to pollution and moisture and are also suitable for use in tropical regions. The transformers do not require special maintenance; only regular cleaning of surface dirt is needed. Terminal boxes are installed at the secondary output terminals of the transformers. There is one hole on the front and one on the side of the terminal box to cooperate with the output terminals for leadout wiring, which is safe and reliable. There are grounding bolts and six installation holes for installation on the product base plate.

    jdzj-18-3-6-10-2.jpg