LZZB9-24/220b/2(4) 24kV Dry Type Current Transformer | Manufacturer
Model and its meaning

Summarize
Measurement accuracy is another crucial aspect of current transformers that cannot be ignored. 15-40.5kV indoor current transformers can achieve measurement accuracy of 0.2 seconds or 0.5 seconds, which is essential for accurately converting large primary currents into controllable secondary currents. This accuracy is critical for electricity metering and current measurement, as it ensures the reliability of the collected data and its practical application value. In an era where energy efficiency and accurate billing are paramount, the role of high-precision current transformers is becoming increasingly prominent.
Current transformers have applications far beyond measurement; they are an integral part of relay protection systems, ensuring the safety of the power grid. By providing accurate current readings, these transformers enable protective relays to operate effectively, ensuring the timely detection and handling of any anomalies in the power system. This protective capability is crucial for preventing equipment damage and maintaining the overall integrity of the power infrastructure.
Normal service condition
Installation site: Indoor.
Ambient temperature: Maximum air temperature 40℃; The minimum temperature is -5℃ . The daily average temperature does not exceed 30℃ .
Atmospheric conditions: There is no severe pollution in the atmosphere.
Technical parameter
LZZB9-24/220b/2 technical parameter table of type Current transformer
|
Product |
Rated primary |
Accuracy |
Rated |
Rated short-term |
Rated dynamic |
|
LZZB9-24/220b/2 |
20 |
0.2/0.2 |
10/10 |
3 |
7.5 |
|
30 |
4.5 |
11.25 |
|||
|
40 |
6 |
15 |
|||
|
50 |
7.5 |
18.75 |
|||
|
75 |
11.25 |
28.125 |
|||
|
100 |
15 |
37.5 |
|||
|
150 |
22.5 |
56.25 |
|||
|
200 |
31.5 |
80 |
|||
|
300 |
45 |
112.5 |
|||
|
400 |
|||||
|
500 |
|||||
|
600 |
0.2/0.2 |
10/10 |
63 |
130 |
|
|
800 |
|||||
|
1000 |
80 |
160 |
|||
|
1200 |
|||||
|
1250 |
|||||
|
1500 |
0.2/0.2 |
10/10 |
100 |
160 |
|
|
1600 |
|||||
|
2000 |
|||||
|
2500 |
LZZB9-24/220b/4 technical parameter table of type Current transformer
|
Product |
Rated primary |
Accuracy |
Rated |
Rated short-term |
Rated dynamic |
|
LZZB9-24/220b/4 |
20 |
0.2/0.2/0.2 |
15/15/20 |
3 |
7.5 |
|
30 |
4.5 |
11.25 |
|||
|
40 |
6 |
15 |
|||
|
50 |
7.5 |
18.75 |
|||
|
75 |
11.25 |
28.125 |
|||
|
100 |
15 |
37.5 |
|||
|
150 |
22.5 |
56.25 |
|||
|
200 |
31.5 |
80 |
|||
|
300 |
45 |
112.5 |
|||
|
400 |
|||||
|
500 |
|||||
|
600 |
0.2/0.2/0.2 |
15/15/20 |
63 |
130 |
|
|
800 |
|||||
|
1000 |
80 |
160 |
|||
|
1200 |
|||||
|
1250 |
|||||
|
1500 |
0.2/0.2/0.2 |
15/15/20 |
100 |
160 |
|
|
1600 |
|||||
|
2000 |
|||||
|
2500 |
Rated secondary current: 5A or 1A.
Rated insulation level: 24/65/125kV.
Structure and characteristics
This series of current transformers are of fully enclosed structure with epoxy resin casting, featuring excellent insulation performance and moisture-proof capability. The product features a compact structure, small size, light weight and easy surface cleaning. A terminal box is installed at the secondary output terminal, which is safe and reliable. There are grounding bolts and six installation holes for installation on the product base plate.