LZZBJ9‑12/175b/2(4) 12kV Indoor Current Transformer for MV Switchgear
Model and its meaning

Summarize
Current transformers must be operated within specified normal operating conditions. They should be installed indoors in a temperature-controlled environment. They are designed to operate within a temperature range of -5°C to 40°C, with an average daily temperature not exceeding 30°C. These conditions are crucial to ensuring the lifespan and reliability of the current transformer, as extreme temperatures can adversely affect its performance and accuracy.
Normal service condition
Installation site: Indoor.
Ambient temperature: Maximum air temperature 40℃ ; The minimum temperature is -5℃. The daily average temperature does not exceed 30℃.
Atmospheric conditions: There is no severe pollution in the atmosphere.
Technical parameter
LZZBJ9-12/175b/2 Type Technical parameter table of Current Transformer
|
Product |
Rated primary |
Accuracy level |
Rated |
Rated short-term |
Rated dynamic |
|
LZZBJ9- |
5 |
0.2/10P10 |
10/15 |
0.6 |
1.5 |
|
10 |
1.2 |
3 |
|||
|
15 |
1.8 |
4.5 |
|||
|
20 |
2.4 |
6 |
|||
|
30 |
3.6 |
9 |
|||
|
40 |
4.8 |
12 |
|||
|
50 |
6 |
15 |
|||
|
75 |
9 |
22.5 |
|||
|
100 |
12 |
30 |
|||
|
150 |
18 |
45 |
|||
|
200 |
21 |
52.5 |
|||
|
300 |
0.2/10P10 |
10/15 |
24.5 |
61.25 |
|
|
400 |
32 |
80 |
|||
|
500 |
|||||
|
600 |
|||||
|
800 |
0.2/10P10 |
15/20 |
50 |
125 |
|
|
1000 |
|||||
|
1200 |
|||||
|
1250 |
|||||
|
1500 |
0.2/10P10 |
15/20 |
63 |
157.5 |
|
|
2000 |
|||||
|
2500 |
|||||
|
3000 |
|||||
|
3150 |
LZZBJ9-12/175b/4 Type Technical parameter table of Current Transformer
|
Product |
Rated primary |
Accuracy level |
Rated |
Rated short-term |
Rated dynamic |
|
LZZBJ9-12/175b/4 |
5 |
0.2/0.2/5P10 |
10/10/20 |
0.6 |
1.5 |
|
10 |
1.2 |
3 |
|||
|
15 |
1.8 |
4.5 |
|||
|
20 |
2.4 |
6 |
|||
|
30 |
3.6 |
9 |
|||
|
40 |
4.8 |
12 |
|||
|
50 |
6 |
15 |
|||
|
75 |
9 |
22.5 |
|||
|
100 |
12 |
30 |
|||
|
150 |
18 |
45 |
|||
|
200 |
21 |
52.5 |
|||
|
300 |
0.2/0.2/5P10 |
10/10/20 |
24.5 |
61.25 |
|
|
400 |
32 |
80 |
|||
|
500 |
|||||
|
600 |
0.2/0.2/5P10 |
10/10/20 |
32 |
80 |
|
|
800 |
50 |
125 |
|||
|
1000 |
0.2/0.2/5P10 |
10/10/30 |
50 |
125 |
|
|
1200 |
|||||
|
1250 |
|||||
|
1500 |
63 |
157.5 |
|||
|
2000 |
|||||
|
2500 |
0.2/0.2/5P10 |
15/15/30 |
63 |
157.5 |
|
|
3000 |
0.2/0.2/5P10 |
15/15/30 |
63 |
157.5 |
|
|
3150 |
Rated secondary current: 5A or 1A, rated insulation level: 12/42/75kV.
Structure and characteristics
This series of current transformers utilizes a fully enclosed epoxy resin cast structure, exhibiting excellent insulation and moisture resistance. Its compact design, small size, and light weight make it easy to clean and maintain. The secondary terminals are equipped with a terminal block for safety and reliability. The baseplate is equipped with a grounding bolt and six mounting holes for flexible installation.


JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits