LZZBW‑10 10kV Outdoor Current Transformer for Medium Voltage Substation
Model and its meaning

Summarize
Current transformer is essential for utilities and industrial facilities requiring precise monitoring of electrical parameters, Its efficient ability to measure current and voltage enables better energy management and resource optimization. Its protective relay function is crucial for protecting electrical equipment from potential overloads and faults, minimizing downtime and maintenance costs.
High measurement accuracy to meet measurement and monitoring needs. Current transformers offer excellent precision for applications requiring high accuracy, such as energy metering and power quality monitoring. They are classified according to standards into different accuracy levels (e.g., Class 0.2 and Class 0.5 for metering, and Class 1 and Class 3 for protection). Within the rated load and rated current range, they accurately reflect the magnitude and phase of the primary current, ensuring accurate energy metering (ensuring fair settlement between power suppliers and users) and reliable monitoring of power system operating status.
Normal service condition
Installation location: Indoor environment only.
Temperature range: maximum ambient temperature 40℃, minimum temperature -25℃, average daily temperature ≤30℃.
Atmospheric standards: The atmospheric environment must be kept clean and free of severe pollution.
Technical parameter
|
Product |
Rated |
Accuracy level |
Rated |
Rated short-term |
Rated dynamic |
|
LZZBW-10 |
5 |
0.2/10P10 |
10/15 |
0.45 |
1.125 |
|
10 |
0.9 |
2.25 |
|||
|
15 |
1.35 |
3.375 |
|||
|
20 |
1.8 |
4.5 |
|||
|
30 |
2.7 |
6.75 |
|||
|
40 |
3.6 |
9 |
|||
|
50 |
4.5 |
11.25 |
|||
|
75 |
6.75 |
16.875 |
|||
|
100 |
9 |
22.5 |
|||
|
150 |
13.5 |
33.75 |
|||
|
200 |
18 |
45 |
|||
|
300 |
24.5 |
61.25 |
|||
|
400 |
24.5 |
61.25 |
|||
|
500 |
32 |
80 |
|||
|
600 |
32 |
80 |
|||
|
800 |
32 |
80 |
|||
|
1000 |
50 |
125 |
Rated secondary current: 5A or 1A, rated insulation level: 12/42/75kV.
Structure and characteristics
This current transformer is designed specifically for outdoor use, featuring a fully enclosed epoxy resin-cast structure that provides excellent insulation and moisture resistance. Its compact structure combines compact size and light weight with an easy-to-clean surface. A dedicated junction box is included for the secondary wiring, and the baseplate is equipped with a grounding bolt. Four mounting holes are also provided to accommodate on-site installation requirements.


JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits