PR Series current transformer,Tape Wrapped,Strong Metal Mounting Base
Feature
■Installation with / without base
■With / without terminal cover
■Low cost
■Rated primary current from 5A to 30000A
Standard
IEC60044-1 GB1208-2006
Technical parameters
|
Rated Frequency |
50/60Hz |
|
Rated Test Voltage |
3kv AC.(1min) |
|
Rated short-time thermal current(Ith) |
60ln |
|
Rated dynamic current |
2.5lth |
|
Rated voltage (Um) |
0.72Kv AC. |
|
Continuous overload (ld) |
1.2ln |
|
Operating temperature |
-10°C~50°C |
|
Housing self-extinguishing class |
VO |
|
Safety factor |
FS 5 |
|
Secondary current |
5A/1A |
Scope of application
The PR Series Protective Current Transformer is specifically engineered to deliver reliable performance under extreme current conditions, making it ideal for power system protection scenarios. Unlike standard measuring current transformers that are primarily designed for nominal operating ranges, this series excels when the system current surges to multiple times the rated working current—whether due to short circuits, load fluctuations, or other transient events. What sets it apart is its ability to maintain stable and accurate electrical characteristics even when operating far beyond the typical measuring range of conventional current transformers, ensuring it remains effective in high-current environments where precision and durability are critical.
When integrated with power protective relays (a core application in power distribution networks, industrial control systems, and electrical infrastructure), the PR Series Protective Current Transformer demonstrates exceptional overload capacity. It retains its key electrical properties—such as ratio accuracy, linearity, and insulation integrity—even when subjected to current levels that are 5 times, 10 times, 20 times, or even higher than its rated working current. This robust overload performance is vital for protective relays to detect abnormal current spikes promptly, trigger appropriate safety actions (e.g., circuit breaking, fault isolation), and safeguard equipment, wiring, and personnel from potential damage caused by overcurrents. Its design thus ensures seamless compatibility with protective relay systems, providing the reliable current sensing needed for robust power system protection.

![]() |
Model |
Current |
Burden |
Dimension(mm) |
||
|
ID |
OD |
HT |
||||
|
PR-30 5P10 |
60/5 |
15 |
30 |
145 |
165 |
|
|
100/5 |
15 |
34 |
100 |
180 |
||
|
PR-34 5P10 |
150/5 |
15 |
34 |
100 |
130 |
|
|
200/5 |
15 |
34 |
100 |
110 |
||
|
PR-45 5P10 |
250/5 |
15 |
45 |
96 |
110 |
|
|
300/5 |
15 |
45 |
96 |
110 |
||
|
PR-60 5P10 |
400/5 |
15 |
45 |
96 |
98 |
|
|
500/5 |
15 |
60 |
100 |
100 |
||
|
PR-68 5P10 |
600/5 |
15 |
68 |
110 |
78 |
|
|
PR-85 5P10 |
800/5 |
15 |
85 |
120 |
78 |
|
|
PR-82 5P10 |
1000/5 |
15 |
82 |
123 |
70 |
|
|
1200/5 |
15 |
82 |
123 |
70 |
||
|
1600/5 |
15 |
82 |
123 |
60 |
||
|
PR-125 5P10 |
2000/5 |
15 |
125 |
178 |
38 |
|
|
2500/5 |
15 |
125 |
178 |
35 |
||
|
PR-120 5P10 |
3000/5 |
15 |
120 |
178 |
35 |
|
|
PR-140 5P10 |
3500/5 |
15 |
140 |
200 |
35 |
|
|
4000/5 |
15 |
140 |
200 |
35 |
||
|
5000/5 |
15 |
140 |
200 |
35 |
||

![]() |
Model |
Current |
Burden |
Dimension(mm) |
||
|
ID |
OD |
HT |
||||
|
PR-34 10P5 |
60/5 |
15 |
30 |
145 |
165 |
|
|
100/5 |
15 |
34 |
100 |
180 |
||
|
150/5 |
15 |
34 |
100 |
130 |
||
|
200/5 |
15 |
34 |
100 |
110 |
||
|
PR-45 10P5 |
250/5 |
15 |
45 |
96 |
110 |
|
|
300/5 |
15 |
45 |
96 |
110 |
||
|
PR-60 10P5 |
400/5 |
15 |
45 |
96 |
98 |
|
|
500/5 |
15 |
60 |
100 |
100 |
||
|
PR-65 10P5 |
600/5 |
15 |
68 |
110 |
78 |
|
|
PR-85 10P5 |
5000/5 |
15 |
140 |
200 |
35 |
|
|
|
Model |
Current |
Burden |
Dimension(mm) |
||
|
ID |
OD |
HT |
||||
|
PR-30 10P10 |
60/5 |
15 |
30 |
145 |
165 |
|
|
PR-34 10P10 |
100/5 |
15 |
34 |
100 |
180 |
|
|
150/5 |
15 |
34 |
100 |
130 |
||
|
200/5 |
15 |
34 |
100 |
110 |
||
|
PR-45 10P10 |
250/5 |
15 |
45 |
96 |
110 |
|
|
300/5 |
15 |
45 |
96 |
110 |
||
|
PR-60 10P10 |
400/5 |
15 |
45 |
96 |
98 |
|
|
500/5 |
15 |
60 |
100 |
100 |
||
|
PR-68 10P10 |
600/5 |
15 |
68 |
110 |
78 |
|
|
PR-85 10P10 |
800/5 |
15 |
85 |
120 |
78 |
|
|
PR-82 10P10 |
1000/5 |
15 |
82 |
123 |
70 |
|
|
1200/5 |
15 |
82 |
123 |
70 |
||
|
1600/5 |
15 |
82 |
123 |
60 |
||
|
PR-125 10P10 |
2000/5 |
15 |
125 |
178 |
38 |
|
|
2500/5 |
15 |
125 |
178 |
35 |
||
|
PR-120 10P10 |
3000/5 |
15 |
120 |
178 |
35 |
|
|
PR-140 10P10 |
3500/5 |
15 |
140 |
200 |
35 |
|
|
4000/5 |
15 |
140 |
200 |
35 |
||
|
5000/5 |
15 |
140 |
200 |
35 |
||


JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits