0102030405
ZW20‑12 Outdoor High‑voltage AC Sectionalizer Vacuum Circuit Breaker
Overview
ZW20‑12 Outdoor High‑voltage AC Sectionalizer Vacuum Circuit Breaker (commonly known as sectionalizing switch) is outdoor distribution equipment rated at 12 kV, 3‑phase AC 50 Hz. It consists of three major components: switch main body, FDR‑01 fault‑detection controller and voltage transformer. It adopts vacuum arc‑extinguishing with SF₆ gas as insulating medium, and is a premium pole‑mounted load switch.
Designed for pole‑mount application on 10 kV feeder lines. When a fault occurs on a T‑connected customer branch or within the customer’s facility, it may cause power outages for the main feeder and other adjacent users. Installing this user‑side sectionalizer at the T‑connection point (responsibility boundary point) is an ideal solution to avoid such cascading failures.
This sectionalizer is capable of making and breaking load current, overload current, short‑circuit current and zero‑sequence current in power systems. It provides overload, short‑circuit, instantaneous trip and earth‑fault protection. Optional multi‑shot auto‑reclosing, local remote control and remote communication functions are available.
Product Features
■ Automatically clear single‑phase earth‑fault
When a single‑phase earth‑fault occurs on the customer branch line, the sectionalizer opens automatically without disturbing the substation and other branch users on the feeder. A built‑in through‑type zero‑sequence current transformer (ratio 20/1, epoxy resin cast) provides earth‑fault current detection.
■ Automatically isolate phase‑to‑phase short‑circuit fault
Upon phase‑to‑phase short‑circuit fault on customer branch, the sectionalizer trips immediately to isolate the faulty line. Two built‑in through‑type protective current transformers (ratio 600/1 or customer‑specified) supply short‑circuit fault current signals.
■ Fast fault‑location
When the sectionalizer trips for branch‑side faults, only the responsible end‑user loses power. Fault information will be reported actively. If communication module is equipped, fault data can be automatically uploaded to power management center.
■ User load monitoring
Optional wired or wireless communication accessories transmit measured data to power management center to realize remote real‑time load monitoring.
■ Loop‑network operation capability, suitable for loop‑network lines.
■ Metering function: detects line voltage, current, frequency and energy consumption, with remote data transmission to management center.
■ Harmonic analysis function, provides reliable reference for grid pollution treatment.
■ Versatile controller configurations:
Supports conventional operation & protection. Optional GSM / GPRS module enables SMS alarm and remote PC control & protection. Hand‑held terminal is also available for switch control, parameter modification and status checking.
■ Reliable sealing performance:
Proven sealed enclosure design with IP67 protection class. The housing is one‑piece die‑drawn for easy sealing, high gas‑tightness and excellent mechanical strength.
■ Maintenance‑free performance:
Main circuit, secondary components and operating mechanism are hermetically sealed inside zero‑gauge‑pressure SF₆ gas compartment. Free from external environmental impacts, stable & reliable with zero maintenance.
■ Excellent cable termination performance:
Cable‑in‑and‑out connection available; patented fluid‑silicone‑rubber angled bushing option delivers superior external insulation.
■ Safe operation:
Explosion‑proof device fitted on top of enclosure, effectively prevents hot gas and debris ejection during switch faults.

JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits