0102030405
ZW32‑12 Outdoor High‑voltage AC Vacuum Circuit Breaker
General Description
ZW32‑12 outdoor high‑voltage AC vacuum circuit breaker is an outdoor power distribution device with rated voltage 12 kV, three‑phase AC 50 Hz.
Designed for pole‑mounted installation, this switch is mainly used to make and break load current, overload current and short‑circuit current in power systems. It provides overload, short‑circuit and instantaneous overcurrent protection. It can be fitted with a single‑side disconnector, double‑side disconnectors, or top‑mounted disconnector.
Product Features
-
Equipped with vacuum interrupter for arc extinction The vacuum interrupter maintains high‑vacuum internal condition, acting as insulation and arc‑extinguishing medium during live operation. When contacts are separated under load by the operating mechanism, vacuum arc is generated between contacts and extinguishes at current zero‑crossing to interrupt circuit current.
-
Adopts air‑silicone rubber and epoxy resin composite insulation; fixed‑pole type is also available.
-
Fully sealed within stainless‑steel or carbon‑steel housing. Excellent sealing performance enables explosion‑proof, anti‑condensation and anti‑pollution functions.
-
Two‑phase or three‑phase current transformers for protection, measurement or metering can be fitted inside the switch.
-
Multi‑ratio current transformers: standard triple ratios are 50 100 150/5, 100 200 300/5, 200 400 600/5. Custom ratios can be supplied according to customer load conditions. Protection accuracy class: 10P10; measurement & metering accuracy class: 0.2S, 0.2, 0.5.
-
Dry‑type voltage transformer can be installed internally to supply operation power and voltage signal sampling.
-
Flexible solution with reserved interfaces for distribution network automation, facilitating smart grid upgrade.
In response to smart‑grid upgrade and function‑expansion requirements, this breaker can be fitted with auto‑recloser controller to realize automatic reclosing. It can work with electronic PT; the battery is charged by CT power supply. Multiple energy‑storage and close‑open operations are achievable under loss‑of‑voltage condition, and operating voltage for external equipment can be output.
Built‑in metering CT/PT supports remote pre‑payment. Zero‑sequence current transformer can be added for earth‑fault protection with sectionalizer controller. Simple remote controller is optional upon request for local remote control at the bottom of utility pole.
-
Optional disconnector Reliable mechanical interlock is provided between the circuit breaker and single‑side / double‑side / top‑mounted disconnector. The disconnector cannot perform close or open operation when the circuit breaker is closed.
-
Housing: stainless steel or ordinary carbon steel. Inrush current controller (2‑phase or 3‑phase, depending on CT quantity) is installed inside to provide overload, short‑circuit and instantaneous overcurrent protection. Current threshold and time delay are adjustable.
-
Operating Mechanism CT‑powered spring mechanism, supports both manual and electric operation.

JDG4-0.5 type voltage transformer,Accuracy class 0.5,designed for voltage measurement and relay protection in indoor AC circuits